A model of fossil fueled plant with once-through boiler for power system frequency simulation studies

Toshio Inoue*, Haruhito Taniguchi, Yasuyuki Ikeguchi T. Inoue, H. Taniguchi

*この論文の責任著者

研究成果: ジャーナルへの寄稿学術論文査読

46 被引用数 (Scopus)

抄録

A model of the fossil fueled generating power plant with once-through boiler for power system frequency simulation studies is presented. In the model, the plant control system is modeled to represent the fundamental response of the coordinated boiler-turbine control in the large-size supercritical plants under change in the system frequency. The model is based on a survey of configurations of the plant control systems used in the major units commercially operated in Japan. The values of the parameters in the model are described through the comparisons with plant responses in a field test and with simulation results from a detailed model of the plant manufacturer. Sample simulation result from the model is presented for demonstrating the fundamental response of the once-through plants under change in system frequency.

本文言語英語
ページ(範囲)1322-1328
ページ数7
ジャーナルIEEE Transactions on Power Systems
15
4
DOI
出版ステータス出版済み - 2000

ASJC Scopus 主題領域

  • エネルギー工学および電力技術
  • 電子工学および電気工学

フィンガープリント

「A model of fossil fueled plant with once-through boiler for power system frequency simulation studies」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル